Terminal Assignment Of The 2Ai I 4Wire Standard - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Terminal assignment
The following table shows the terminal assignment of the 2AI I 4WIRE Standard for
the various terminal modules:
Table 12-42 Terminal assignment of the 2AI I 4WIRE Standard
View
CH0
M
0+
1
5
M
0--
2
6
24 VDC
3
7
M
ana
4
8
CH0
M
0+
1
5
M
0--
2
6
24 VDC
3
7
M
ana
4
8
A
A
AUX1
4
8
A
A
AUX1
3
7
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Terminal assignment
TM-E15S24-01 and 2AI I 4WIRE Standard
4-wire
CH1
M
1+
mA
mA
M
1--
24 VDC
M
ana
TM-E15S26-A1 and 2AI I 4WIRE Standard
4-wire
CH1
M
1+
mA
mA
M
1--
24 VDC
M
ana
AUX1
AUX1
Analog Electronic Modules
Remarks
Channel 0: Terminals 1 to 4
Channel 1: Terminals 5 to 8
M+: Input signal "+"
M--: Input signal "--"
DC 24V: Power supply for
4-wire measuring transducer
M
: Ground (from power
ana
module)
The 4-wire transducers are
powered from the module.
Channel 0: Terminals 1 to A3
Channel 1: Terminals 5 to A7
M+: Input signal "+"
M--: Input signal "--"
DC 24V: Power supply for
4-wire measuring transducer
M
: Ground (from power
ana
module)
The 4-wire transducers are
powered from the module.