Commissioning and diagnostics

4.1

Configuring the ET 200S

Introduction
This section describes how to configure and assign parameters to the ET 200S:
● Configuration: The systematic arrangement of the different ET 200S modules (setup)
● Parameter assignment: Setting the ET 200S parameters using the configuration software
Configuration
The ET 200S has address space of up to 255 bytes for inputs and 255 bytes for outputs. To
better exploit the available address space of the scanner and reduce data transfer between
the ET 200S and the scanner, you can group several electronic modules/load feeders in a
single byte in the input or output area of the process image. This is achieved by the
systematic arrangement and designation of the ET 200S electronic modules/motor starters.
In Appendix C, you will find a table giving the address space required for the individual
modules.
You can group the following module types in a single byte:
● Digital input modules
● Digital output modules
● Motor starters (direct-on-line starters and reversing starters)