Siemens SIMATIC ET 200S Manual page 342

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Digital Electronic Modules
Technical data
Dimensions and weight
Dimensions W x H x D
(mm)
Weight
Module-specific data
Supports clock synchro-
nized mode
Number of inputs
Cable length
Unshielded
shielded
Voltages, currents, electrical potentials
Rated supply voltage (from
power module)
Polarity reversal
protection
Electrical isolation
Between the channels
Between channels and
backplane bus
Permissible potential differ-
ence
Between different
circuits
Insolation tested with
Current consumption
From power supply
Power loss of the module
Status, interrupts, diagnostics
Status display
Interrupts
Process alarm
Diagnostic functions
Group error
Reading of diagnostic
data
11-22
15 x 81 x 52
Approx. 35 g
Yes
2
max. 600 m (164 ft)
max. 1,000 m (164
ft)
24 VDC
Yes
No
Yes
75 VDC / 60 VAC
500 VDC
Dependent on the
sensor
Typical 0.4 W
Green LED per
channel
Configurable
1)
red LED "SF"
Yes
Sensor power supply output
Output voltage
Loaded
Output current
Rated value
Permitted range
Short-circuit protection
Data for selecting an sensor
Input voltage
Rated value
for "1" signal
for "0" signal
Input current
For signal "1"
Input delay
(configurable)
"0" to "1" transition
"1" to "0" transition
Input characteristic curve
Connection of 2wire
BEROs
permitted quiescent
current
per module
ET 200S Distributed I/O System
Min. L+ (--0.5 V)
500 mA
0 to 500 mA
1)
Yes, electronic
24 VDC
11 to 30 V
--30 to 5 V
Typical 8 mA
0.1 ms
(0.05 to 0.15 ms)
0.5 ms
(0.4 to 0.6 ms)
3 ms
(2.7 to 3.3 ms)
15 ms
(14.85 to 15.15 ms)
0.1 ms
(0.05 to 0.15 ms)
0.5 ms
(0.4 to 0.6 ms)
3 ms
(2.7 to 3.3 ms)
15 ms
(14.85 to 15.15 ms)
To IEC 61131,
type 1
possible
max. 1.5 mA
EWA-4NEB 780602402-12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents