Siemens SIMATIC ET 200S Manual page 499

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Analog Value Formation
Measurement principle
Integration / conversion
time / resolution per
channel:
Integration time
selectable
Interference frequency
suppression in Hz
Integration time in ms
Basic conversion time
incl. integration time in
ms
Additional conversion
time for wire break
diagnostics in ms
Cycle time in ms
Resolution (incl.
overshoot range)
Interference Suppression, Error Limits
Interference voltage sup-
pression for f= n x (f11%),
(f1 = interference
frequency)
Common mode
interference (U
)
SS
Common mode
interference
(peak value of
interference < rated
value of the input range)
Crosstalk between inputs
Operational error limits
(across complete tempera-
ture range, in relation to in-
1
put range)
Basic error limit (operational
error limit at 25 _C, related
1)
to the input range)
Temperature error (in rela-
tion to input range)
Linearity error (relative to
the input range)
Repetition accuracy
(in transient state at 25_C,
relative to input range)
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
integrating
Yes
60
50
16.7
20
55
65
20
20
Number of active
channels per
module x conversion
time
15 bits + sign
min. 90 dB
min. 70 dB
min. --50 dB
0.6 %
0.4 %
0.005 %/K
0.01 %
0.05 %
Analog Electronic Modules
Data for selection of the sensor
Input range (rated
value)/input resistance
Voltage
Thermocouple
Permitted continuous input
voltage (destruction limit)
Connection of signal
generators
For voltage
measurement
Characteristics linearization
Temperature compensation
Internal temperature
compensation
External temperature
compensation by
looping a compensation
unit into the measuring
circuit
External compensation
by means of
temperature value
acquired at an analog
module of the same
ET 200S station
Smoothing of measured
values
Level
weak
medium
strong
1)
with Type N: from --150 _C, Type B:
from 200 _C,
Type T: from --230 _C
80 mV/min. 1 MΩ
Type E, N, J, K, L, S,
R, B, T/min. 1 M
10 V, continuous
possible
Yes, configurable for
Type E, N, J, K, L, S,
R, B, T as per
IEC 584
Not possible
Possible, one
external
compensation
unit per channel
Yes
Yes, configurable in
4 stages by digital
filtering
Time constant
No
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
12-93