Wire break in the actuator wiring
1. Remove the cable from terminal 1 on the 2DO 24 VDC/0.5A HF electronic
module (slot 7)
2. Monitor the status LEDs
IM151-3 PN:
-- SF: lit
2DO 24 VDC/0.5A HF electronic module:
-- SF: lit ⇒ diagnostic message exists
-- 1: Off ⇒ The output is not activated
3. Evaluate diagnostic data set C00A
Byte
Header information
0 and 1
2 and 3
4 and 5
Channel diagnostic data
6 and 7
8 and 9
10 and 11
12
13
14 and 15
Channel diagnostic data record 0 with detailed information on the problem
16 and 17
18
19
20 and 21
4. Attach the cable to the actuator again in terminal 1 and evaluate the diagnosis
again:
Status LED IM151-3 PN:
-- SF: Off
Status LEDs on the 2DO 24 VDC/0.5A High Feature electronic module:
-- SF: Off
-- 1: off/on
-- The diagnosis is deleted.
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Contents
0010
Data record with channel diagnostics
H
0012
18 bytes follow
H
0100
Version 1.0
H
0007
Slot 7
H
0001
Submodule slot 1
H
8000
Error on submodule
H
08
entering state
H
00
Reserved
H
8000
Submodule diagnostic information exists
H
0000
Channel 0
H
48
Error entering state at an output
H
01
Data format: 1 bits
H
0006
Wire break
H
Brief Instructions on Commissioning ET 200S
.