• Parameterize the interface module as follows:
Interface module
IM 151-1
STANDARD
or
or
IM 151-1 FO
STANDARD
Note
If "Operation at Preset < > Actual Configuration" is blocked at parameter
assignment, the following occurs:
The ET 200S does not start up if a module is missing or if an incorrect module
is inserted. A diagnostic report is output to the effect that there is no module or
the module is incorrect.
The ET 200S starts up if you enable option handling for the slot of an inserted
RESERVE module. A diagnosis is not reported.
If you have parameterized an electronic module for the RESERVE module, the
following substitute values are reported:
-- Digital Input Modules: 0
-- Analog Input Modules: 7FFF
-- Function Module: 0
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters
Option
Enable
handling,
general
Option
Enable (all the
handling: Slots
slots on which
2 to 63
RESERVE
modules can be
located)
H
Configuration Options
Setting
Option handling is activated
for the whole ET 200S.
There is a RESERVE module
or configured electronic
module on the slot. A
diagnosis is not reported.
Description
3-39