The following applies with temperature measurements: The existing slope of the
characteristic line is retained in the over or under controller range when leaving the
linearized nominal range.
12.1.2
Analog value visualization for measurement ranges of the
analog input modules in SIMATIC S7 format
Introduction
The tables in this section contain the digitized analog values for the measuring
ranges of the analog input modules.
Since the binary representation of the analog values is always the same, these
tables contain only a comparison of the measuring ranges with the units.
Voltage measuring ranges:
Table 12-4 SIMATIC S7 Format: Measuring ranges 80 mV, 2.5 V, 5 V and 10 V
Measuring
Measuring
range
range
80 mV
 2.5 V
> 94,071
> 2,9397
94,071
2,9397
:
:
80,003
2,5001
80,000
2,5
60,000
1,86
:
:
-- 60,000
-- 1,86
-- 80,000
-- 2,50
-- 80,003
-- 2,5001
:
:
-- 94,074
-- 2,9397
< -- 94,074
< -- 2,9397
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
80 mV, 2.5 V, 5 V, 10 V
Measuring
Measuring
range  5 V
 5 V
range
 10 V
> 5,8794
> 11,7589
5,8794
11,7589
:
:
5,0002
10,0004
5,00
10,00
3,75
7,50
:
:
-- 3,75
-- 7,50
-- 5,00
-- 10,00
-- 5,0002
-- 10,0004
:
:
-- 5,8796
-- 11,759
< -- 5,8796
< -- 11,759
Analog Electronic Modules
Units
decimal
hexadeci-
mal
32767
7FFF
H
32511
7EFF
H
:
:
27649
6C01
H
27648
6C00
H
20736
5100
H
:
:
--20736
AF00
H
--27648
9400
H
--27649
93FF
H
:
:
--32512
8100
H
--32768
8000
H
Area
Overflow
Overshoot
range
range
Nominal
range
Undershoot
range
range
Underflow
12-5