The channel-specific diagnosis for the ET 200S with the IM151-1 STANDARD,
IM151-1 FO STANDARD and IM151-1 HIGH FEATURE is structured as follows:
Byte 35
Byte 36
Byte 37
Bytes 38
to 40
Max. byte 61
max. byte 109
max. byte 127
Figure 6-26
Note
The module slot is encrypted in byte 16/35, bit 0 to 5. The following applies:
displayed number +1 ≙ slot of the module (0 ≙ slot 1; 1 ≙ slot 2; 3 ≙ slot 4,
etc.)
In bits 6/7 of byte 17/36, 00
channel-specific diagnosis.
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
7
6 5 4
3 2
1
0
1 0
000000
up to 111111
B
channel-specific diagnosis.
Code for channel-specific diagnosis
7
6 5 4
3 2
1
0
000000
up to 000011
B
diagnosis
01
: Input channel
B
10
: Output channel
B
11
: Input/output channel
B
7
6 5 4
3 2
1
0
Error type (see Table 6-12 to Table 6-23)
Channel
001
: Bit
B
type:
010
: 2 bits
B
011
: 4 bits
B
100
: Byte
B
101
: Word
B
110
: 2
B
words
Next channel-specific diagnostic message
(assignment as for bytes 35 to 37)
in DPV0 mode: IM151-1, IM151-1 FO STANDARD, IM151-1
HIGH FEATURE
in DPV1 mode: IM151-1, IM151-1 FO STANDARD,
in DPV1 mode: IM151-1 HIGH FEATURE
Structure of the channel.specific diagnosis for the ET 200S with the IM151-1
STANDARD, IM151-1 FO STANDARD and IM151-1 HIGH FEATURE
is output if a power module reports a
B
Commissioning and Diagnostics
Bit no.
: Module slot that sends the
B
Bit no.
: Number of the channel that sends the
B
Bit no.
6-39