Diagnostics
In the event of a fault, OB 82 is started. In OB 82 start SFB 52. Evaluate the
diagnostic data set C00A
Switching off the load voltage on the power module
1. Switch off the load voltage on the PM-E 24VDC (slot 1).
2. Monitor the status LEDs
IM151-3 PN:
-- SF: lit
Power module:
-- PWR: off ⇒ No load voltage at power module
-- SF: lit ⇒ diagnostic message exists.
I/O modules in the potential group:
-- LEDs: lit
3. Evaluate diagnostic data set C00A
Byte
Header information
0 and 1
2 and 3
4 and 5
Channel diagnostic data
6 and 7
8 and 9
10 and 11
12
13
14 and 15
Channel diagnostic data record 0 with detailed information on the problem
16 and 17
18
19
20 and 21
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
.
H
Contents
0010
Data record with channel diagnostics
H
0012
18 bytes follow
H
0100
Version 1.0
H
0001
Slot 1
H
0001
Submodule slot 1
H
8000
Error on submodule
H
08
Entering state
H
00
Reserved
H
8000
Submodule diagnostic information exists
H
0000
Channel 0
H
28
Error entering state at an input
H
01
Data format: 1 bits
H
0011
Encoder or load voltage missing
H
Brief Instructions on Commissioning ET 200S
.
H
Meaning