Technical data
Dimensions and weight
Dimensions
W x H x D (mm)
Weight
Module-specific data
Supports clock synchro-
nized mode
Number of outputs
Cable length
•
Unshielded
•
shielded
Voltages, currents, electrical potentials
Rated power supply voltage
L+ (from power module)
Reverse polarity protection
current per channel
•
to 50°C
•
to 60°C
Electrical isolation
•
Between the channels
•
Between channels and
backplane bus
•
Between channels and
backplane bus
•
Between power supply
voltage and backplane
bus
Permissible potential differ-
ence
•
Between power supply
voltage and backplane
bus
•
Between channels and
backplane bus
•
Between channels and
power supply voltage
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
15 x 81 x 52
Approx. 50 g
No
2
max. 600 m (164 ft)
max. 1,000 m
(164 ft)
24 V DC
Yes
Max. 5 A
Max. 4 A
Yes
Yes
Yes
Yes
75 VDC / 60 VAC
240 VAC
240 VAC
Digital Electronic Modules
Isolation tested
•
Between power supply
voltage and backplane
bus
•
Between channels and
backplane bus
•
Between channels and
power supply voltage
Current consumption
•
from L+ power supply
Power loss of the module
Status, interrupts, diagnostics
Status display
Diagnostic functions
Data for selection of an actuator
Output current
•
Continuous thermal
current
•
Minimum load current
•
Minimum voltage
Connecting 2 outputs in
parallel
•
For redundant triggering
of a load
•
To increase
performance
Actuation of a digital input
Switching frequency
•
with ohmic load
•
with inductive load
•
With lamp load
Limitation (internal) of the
inductive disconnection
voltage
Short-circuit protection of
1)
the output
1)
The relay outputs must be fuse-protected with
6 A externally.
Yes
500 VDC
1500 VAC
1500 VAC
max. 30 mA
Typical 0.6 W
Green LED pro
Channel
No
Max. 5 A
8 mA
17 V
No
No
Yes
2 Hz
0.5 Hz
2 Hz
No
No
11-79