Siemens SIMATIC ET 200S Manual page 512

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Analog Electronic Modules
Analog Value Formation
Resolution (including sign)
Conversion time (per
channel)
Settling time
For resistive load
For capacitive load
For inductive load
Interference Suppression, Error Limits
Crosstalk between outputs
Operational error limits
(across the temperature
range, in relation to output
range)
Basic error limit (operational
error limit at 25 _C, related
to the output range)
Temperature error (in
relation to output range)
Linearity error (in relation to
output range)
Repetition accuracy (in
transient state at 25 _C,
relative to output range)
Output ripple, bandwidth 0
to 50 kHz (in relation to
output range)
12-106
10 V/ 16 Bit
¦
1 to 5 V/14 bits
Max. 1.0 ms
0.1 ms
0.5 ms
0.5 ms
> 60 dB
0.07 %
0.03 %
0.001 %/K
0.02 %
0.01 %
0.02 %
Data for selection of the actuator
Output range (nominal
value)
Load impedance (in the
nominal range of the
output)
With voltage
outputs
Capacitive load
Voltage output
Short-circuit protection
Short-circuit current
Destruction limit for
externally applied
voltages/currents
Voltage measured
between the outputs
and M
ANA
Current
Connection of actuators
Voltage output
2-wire connection
4-wire connection
ET 200S Distributed I/O System
 10 V
1 to 5 V
Min. 1.0 kΩ
max. 1 µF
Yes
Approx. 25 mA
Max. 15 V
continuous, 75 V for
max. 1 s (sampling
ratio 1:20)
max. DC 50 mA
Possible, without
compensation of
cable resistance
possible
EWA-4NEB 780602402-12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents