Mechanical environmental conditions
The mechanical environmental conditions are shown in the following table in the
form of sinusoidal oscillations.
ET 200S modules
Everything except motor
starters
Testing mechanical environmental conditions
The following table provides information on the type and extent of tests of
mechanical environmental conditions.
Test for ...
Test Standard
Oscillations
Oscillation test in
accordance with
IEC 60068-2-6
Shock
Shock tested to
IEC 60068-2-27
Repetitive
Shock tested to
shock
IEC 60068-29
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Frequency
Permanent
range
10 ≤ f ≤ 58Hz
0.15 mm amplitude
58 ≤ f ≤ 150Hz
2g constant acceleration
Terminal modules and electronic modules
Vibration type: Frequency sweep with a rate of change of 1 octave/min-
ute.
10 Hz ≤ f ≤ 58 Hz, constant amplitude 0.35 mm
58 Hz ≤ f ≤ 150 Hz, constant acceleration 5g
Vibration duration: 20 frequency sweeps per axis in each of the
3 mutually vertical axes
Type of shock: Half-sine
Type of shock: 15 g peak value, duration of 11 ms
Type of shock: 3 shocks each in +/-- direction in each of the
3 mutually vertical axes
Type of shock: Half-sine
Type of shock: 25 g peak value, duration of 6 ms
Type of shock: 10003 shocks each in +/-- direction in each of the 3
mutually vertical axes
General Technical Specifications
Occasional
0.35 mm amplitude
5g constant acceleration
7-9