Ao U Standard Analog Electronic Module (6Es7 135-4Fb00-0Ab0) - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Internal compensation with TM-E 15S24-AT or TM-E15C24-AT
Factors that influence the precision of the temperature measurement
Rules for use of the internal
temperature compensation
Supplementary technical
specifications for the error
li it
limits of the 2A TC High
f th 2A TC Hi h
Feature
*
The static state is defined with a virtually constant ambient temperature (e.g. there is no air
flow in the enclosed switch cabinet).
12.18
2AO U Standard analog electronic module
(6ES7 135-4FB00-0AB0)
Order number
6ES7 135-4FB00-0AB0
Properties
• 2 outputs for voltage output
• Output range:
--
10 V, resolution 13 bits + sign
¦
-- 1 to 5 V, resolution 12 bits
• Isolated for load voltage L+
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
The connected channel with internal compensation must
be configured separately.
Do not install the 2AI TC High Feature immediately
adjacent to a power module with high infeed current
(> 3 A). With an infeed current of 10 A an additional error
of 2 K may occur.
The station must be in a static state* to reach the specified
precision.
The precision is reached 30 minutes after entry to the
static state.
The total error of the channel results from the addition of
the input error and the error from the internal
compensation.