Mechanical Installation

4 Mechanical Installation

4.1 Items Supplied

Items supplied can vary according to product configu-
ration.
4
4
Make sure that the items supplied and the
information on the nameplate correspond to the
order confirmation.
Visually check the packaging and the drive for
damage caused by inappropriate handling during
shipment. File any claim for damage with the
carrier. Retain damaged parts for clarification.
VLT
1
T/C: FC-302N710T7E21H2XGC7XKSXXXXA0BXCXXXXD0
2
P/N: 131N2885
3
710 kW / 750 HP, High Overload
IN: 3x525-690V 50/60Hz 743/711 A (CE)
4
IN: 3x525-600V 50/60Hz 743/711 A (UL)
5
OUT: MOTOR 3x0-Vin 0-500Hz 763/730 A
800 kW / 950 HP, Normal Overload
IN: 3x525-690V 50/60Hz
IN: 3x525-690V 50/60Hz
OUT: MOTOR 3x0-Vin 0-500Hz
IP21 / TYPE 1
Tamb. 45 C/113 F at Full Output Current
Tamb. 55 C/131 F at Full Output Current Derating
SCCR 100 kA at UL Voltage range 525-600 V
ASSEMBLED IN USA
6
1
Type code
2
Part number and serial number
3
Power rating
Input voltage, frequency, and current (at low/high
4
voltages)
Output voltage, frequency, and current (at low/high
5
voltages)
6
Discharge time
Illustration 4.1 Product Nameplate for E2h Enclosure (Example)
NOTICE
Removing the nameplate from the drive can result in the
loss of warranty.
12
VLT® AutomationDrive FC 302
AutomationDrive
R
www.danfoss.com
S/N:
123456H123
866/828 A (CE)
866/828 A (UL)
889/850 A
Listed 36U0 E70524 IND. CONT. EQ.
UL Voltage range 525-600 V
Danfoss A/S
6430 Nordborg
Denmark
CAUTION - ATTENTION:
See manual for special condition / prefuses
Voir manuel de conditions speciales / fusibles
`
WARNING - AVERTISSEMENT:
Stored charge, wait 40 min.
Charge residuelle, attendez 40 min.
`
Danfoss A/S © 04/2018 All rights reserved.

4.2 Tools Needed

Receiving/unloading
I-beam and hooks rated to lift the weight of the
drive. Refer to chapter 3.2 Power Ratings, Weights,
and Dimensions.
Crane or other lifting aid to place the unit into
position.
Installation
Drill with 10 mm or 12 mm drill bits.
Tape measurer.
Various sizes of Phillips and flat bladed
screwdrivers.
Wrench with relevant metric sockets (7–17 mm).
Wrench extensions.
Torx drives (T25 and T50).
Sheet metal punch for conduits or cable glands.
I-beam and hooks to lift the weight of the drive.
Refer to chapter 3.2 Power Ratings, Weights, and
Dimensions.
Crane or other lifting aid to place the drive onto
pedestal and into position.

4.3 Storage

Store the drive in a dry location. Keep the equipment
sealed in its packaging until installation. Refer to
chapter 9.4 Ambient Conditions for recommended ambient
temperature.
Periodic forming (capacitor charging) is not necessary
during storage unless storage exceeds 12 months.
MG38A202