Superheat controller, type EIM 365 (PV01)

Installation

Technical specification
Table 3: Technical specification
Features
Supply voltage
Power consumption
Input signals
EEV Driver
Data communication
Environmental conditions
Dimensions
Battery backup
Operation
Connector type
Gateway
Display
PC suite
© Danfoss | Climate Solutions | 2022.09
Description
24 V AC / DC (± 15%), 50 / 60 HZ Galvanically Isolated
Idle: Max. 20 mA @ 24 V DC
Operating: Max. 900 mA RMS @ 24 V DC
Po
S2
S4
Max. current 900mA RMS
Supported valves:
ETS 12.5, 25, 50, 100, 250, 400; ETS 6, CCMT 16-42; CTR; ETS Colibri 12-100C and User defined
Type
Baud rate
Address settings
Connector
Internal Termination
Galvanic isolation
Storage
Operating
Humidity
25 × 50 × 80 mm / 0.98 × 1.97 × 3.15 inch
18 – 28 V DC, > 49 VmAh (Recommend using Danfoss EKE 2U)
Standalone or via MODBUS data communication
4 way Mini fit receptacle Molex 39-01-2040 or similar
2 way Mini fit receptacle Molex 39-01-2020 or similar
Crimp: 24- 18 AWG Molex 39-020-0039 or similar.
Standard RS485 to USB convertor. (eg; ADAM-4561, ICP DAS I-7561U-G)
Note: check compatibility of gateway tool with PC operating system
None
None (EIM 365 is to be connected and configured using supervisor systems).
AKS 32R (or similar Ratiometric pressure transmitter)
Measuring range: -60 – +120 °C / -76 – 248 °F
PT1000 or Digital input from external contact.
RS485 – Modbus RTU (Not terminated internally)
19200
Selectable via Software (default 164)
Pluggable
No
No
-34 °C to 71 °C / -30 °F to 160 °F
-25 °C to 60 °C / -13 °F to 140 °F
<95% RH, non-condensing
BC415322248492en-000101 | 5