F4–08DA–2 8-Ch. Analog Voltage Output
Sequencing
Example 1,
D4–440/450
5
4
4
430
440
450
The following program example shows how to send digital values to the module
when you have more than one channel. This example assumes you have already
loaded the data according to the following table. It is important to use the rungs in
the order shown for the program to work. This example will not work with D4–430
CPUs.
V-Memory Locations for Output Data in Examples 1 and 2
Channel Number
1
V–Memory Storage
3000
Ch8 Done
C10
Ch7 Done
C7
Ch6 Done
C6
Ch5 Done
C5
Ch4 Done
C4
2
3
4
3001
3002
3003
C0
When channel 8 is updated, C0 restarts the update
OUT
sequence.
When channel 7 has been updated, this rung loads
LD
the data for channel 8 into the accumulator.
V3007
C10
Turning on C10 triggers the channel update (see
OUT
the channel select rungs).
When channel 6 has been updated, this rung loads
LD
the data for channel 7 into the accumulator.
V3006
C7
Turning on C7 triggers the channel update (see the
OUT
channel select rungs).
When channel 5 has been updated, this rung loads
LD
the data for channel 6 into the accumulator.
V3005
C6
Turning on C6 triggers the channel update (see the
OUT
channel select rungs).
When channel 4 has been updated, this rung loads
LD
the data for channel 5 into the accumulator.
V3004
C5
Turning on C5 triggers the channel update (see the
OUT
channel select rungs).
5
6
7
3004
3005
3006
3007
8