Module Resolution
16-Bit (Unipolar
Voltage Input)
4
4 4
430 440 450
Module Resolution
15-Bit Plus Sign
(Bipolar Voltage
Input)
4
4 4
430 440 450
Unipolar analog signals are
converted into 65536 counts
ranging from 0 to 65535 (2
For example, with a 0 to 156mV
signal range, 78mV would be
32767. A value of 65535 repre-
sents the upper limit of the
range.
Unipolar Resolution + H * L
H or L = high or low limit of the range
The module has 16-bit unipolar
or 15-bit + sign bipolar resolu-
tion. Bipolar analog signals are
converted into 32768 counts
ranging from 0 to 32767 (2
For example, with a –156mV to
156mV signal range, 156mV
would be 32767. The bipolar
ranges utilize a sign bit to pro-
vide 16-bit resolution. A value of
32767 can represent the upper
limit of either side of the range.
Use the sign bit to determine
negative values.
Bipolar Resolution + H * L
32767
H or L = high or low limit of the range
F4-08THM 8-Channel Thermocouple Input
5V
156mV
16
).
2.5V
78 mV
0V
0 V
65535
156 mV
5 V
15
).
0 V
0 V
–156 mV
–5 V
32767
0
32767
65535
Counts
0
32767
Counts
10–19
Need help?
Do you have a question about the DL405 and is the answer not in the manual?