Technical Data - Siemens CP-8000 User Manual

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

System Components and Technical Data

5.7.1.2.2 Technical Data

Binary outputs
8 binary outputs
(relay)
Nominal voltage
Maximum continuous current
Switching capacity
Switching cycles
Output circuits
Rated impulse voltage
Connectors
Terminals
*)
with parallel connection
·
For power augmentation 2 relays may be connected parallel, this must happen within one
group (applies only for I < 6 A → 2 x 3 A)
·
Groups with parallel connection must not be next to another
·
Next to a group with parallel connection outputs may be loaded only with £ 2 A
·
Outputs that are loaded with > 3 A must not be next to another;
exception: with power augmentation the outputs of one group must be used
·
Groups that are loaded with > 2 A should not be next to another;
example: 3 A-3 A-1 A-1 A-3 A-3 A-1 A-1 A instead of 3 A-3 A-3 A-3 A-1 A-1 A1 A-1 A
146
Unrestricted
· 4 groups with 2 outputs each
· Each relay has a 1-pole normally-open contact
· The outputs are galvanically insulated from logic circuits and
ground by monostable relays with double insulation
· Each group is galvanically insulated from the other groups,
logic circuits and ground with double insulation
· Within the groups the outputs are galvanically insulated with
operational insulation (250 kV)
· The Outputs can be used for switching of direct voltage or also
alternating voltage
· Function and status of the outputs via display
· 24/48/60/110/220 VDC
· 110/230 VAC
Standard circuitry
· 8 outputs max. 2 A each (5 A/1 min)
Circuitry with derating resp. for switching capacity 6 A
· 4 outputs max. 3 A each, 4 outputs max. 1 A each
Circuitry with derating at 5 A
· 1 output max. 5 A, 7 outputs max. 1 A each
· 2 output max. 5 A each, 6 outputs max. 0 A each (relay must
not be activated)
DC voltage
· Min. 50 mW at 5 VDC
· Max. acc. to diagram
AC voltage
· Max. 1250 VA
5 A/250 VAC, resistive load
· Max. 500 VA
2 A/250 VAC, cosj = 0.4
· 3x10
4
Max. 250 VDC/253 VAC (operated with an external voltage)
4 kV
Removable screw terminals (grid size 5.08)
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
*)
DC8-037-2.02, Edition 10.2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp-8021Cp-8022

Table of Contents