Siemens CP-8000 User Manual page 388

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

Engineering via SICAM WEB
Processing type
AI_U – voltage value
acqisition
388
Unrestricted
Parameter
Processing grid
X_0%
X_100%
Y_0%
Y_100%
Smoothing
MV_conv_free_Xl
zero_range_Xzu
zero_range_Xzl
zero_range_Yz
zero_range_a MV_conv
OV_suppr_t
standard load
line frequency
Zero range
thresh_additive
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Meaning
Processing grid in seconds
0.1 to 25.5
Nominal range in the physical unit of the
input/output (0%) (S)
-50.0 to 50.0
Nominal range in the physical unit of the
input/output (100%)
-50.0 to 50.0
Technological or normalized value 0% (S)
-1000000000000000.000 to
1000000000000000.000
Technological or normalized value 100% (S)
-1000000000000000.000 to
1000000000000000.000
0 - 99 in %. 0% = no smoothing, 99% = high-
est possible smoothing
0 to 99
Limit of not plausible range. Parameter is only
effective, if the parameter ze-
ro_range_a_MV_conv is set to free
parametrizable (in the physical unit of the
input) (S)
-103.00 to 103.00
Upper limit of zero range in % of X_100% (S)
-103.00 to 103.00
Lower limit of zero range in % of X_100% (S)
-103.00 to 103.00
Technological or normalized value of zero
range (S)
-1000000000000000.000 to
1000000000000000.000
Zero range suppression (and check of the
plausibility limits) either standard or free
parametrizable (S)
· Standard
· Free configurable
OV suppression time in seconds, 0=no OV
suppression
0 to 255
The measuring range can be adapted with
changing the load (S)
NO/YES
The noise rejection takes place for the
parametrized line frequency
· 50 Hz
· 60 Hz
· 16.7 Hz
Zero range suppression (and check of the
plausibility limits) (S)
NO/YES
Change threshold in % of X_100% (S) AI_T:
% of temperature range
0 to 1000.0
DC8-037-2.02, Edition 10.2017