Siemens CP-8000 User Manual page 364

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

Engineering via SICAM WEB
Category
Redundancy return in-
formation message
Selective data flow rout-
ing
364
Unrestricted
Parameter
PRE_(RED)
Priority_(RED)
SID-BSE
SID-ST
SID-SSE
Return_information_function_
(RED)
BSE_(RED)
PRE_(RED)
PRE
Station
Data_class
Periodical transfer
Event_data
Time_tag
Function_group
address-conversion
Change_sign_of_measured_
values
New_CASDU1
New_CASDU2
New_IOA1
New_IOA2
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Meaning
Protocol element number
Priority 0 (lowest)...priority 14 (highest)
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
· Redundancy state
· Switchover runs at a global switchover
· Keyswitch of the SCA-RS: system A active
· Keyswitch of the SCA-RS: automatic
· Keyswitch of the SCA-RS: system B active
· Listening mode
Basic system element
Protocol element number
Protocol element number (0...3)
0...99 = selective station
unused = single-point-PRE or multi-point-
PRE to all remote stations
· Data class 1
· Data class 2
Selection periodical level or no periodical
transfer
Transfer with or without time tag
0 = yes, 1 = no
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
New address of the datapoint. The complete
address consists of new CASDU1, CASDU2,
IOA1, IOA2 and IOA3. New CASDU1 and
CASDU2 = 255 means no address-
conversion.
DC8-037-2.02, Edition 10.2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp-8021Cp-8022

Table of Contents