Function Packages
Blocking and Enabling of Messages with Process Information and Periodical
Information
The copy operation of messages with process information and periodical information can be
blocked and enabled:
·
in the input-side process images
·
in the output-side process images
This can take place with the following granularity:
·
Per message
·
All messages
·
Per periodical information
·
I/O Master Module
Changing the Execution Status of the Open-/Closed-Loop Control Function
·
Halt and continue program
·
Perform cold start or warm start of the program
Test Means
The available test means are:
(a) Halting of the execution due to a trigger condition (breakpoint)
(b) Execution of the task in cycle steps
The function (a) is not supported by SICAM WEB.
For the function (a) a trigger condition is defined in the tool "CAEx plus Online Test". A trigger
conditions consists of up to 4 conditions. The conditions of a trigger condition are combined
equal-ranking with AND or OR.
A condition compares a variable with a constant value to be specified:
Variable of the Type
BOOL
INT or REAL
The function "halting the execution due to a trigger condition" halts the task, if the trigger con-
dition is satisfied. The trigger condition is evaluated at the end of the task.
Display Statistic Information
The following information on the application program is made available:
·
Parameterized cycle time
·
Current run time
·
Maximum run time
·
Number of time-outs that the system has registered
·
Used memory space
·
Compiler errors
During the course of the interrogation, the current run time and the number of time-outs can
be optionally reset (does not apply for SICAM WEB).
72
Unrestricted
Condition
variable <operator> value
variable <operator> value
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
<operator>
=
<
=
<>
DC8-037-2.02, Edition 10.2017
<>
>