Installation and Circuitry
6.4.1.1

Space Requirement with SICAM I/O Modules

If the device is extended by external SICAM I/O Modules (max. 6 are permitted), then you
must consider the width of the coupling module, the number of used I/O Modules and the end
clamp.
Example: CP-8000 + 6 ext. SICAM I/O Modules
Thermical space ...................................................... 30
CP-8000 ............................................................... 128
CM-8811 coupling module .................................... 12,5
6 SICAM I/O Modules (6 x 30) ............................... 180
End clamp .................................................................5
Horizontal space requirement (mm) .................... 355,5