E.2 Usage As Telecontrol Substation With Node Function (Protocol Converter) - Siemens CP-8000 User Manual

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

E.2
Usage as Telecontrol Substation with Node Function
(Protocol Converter)
Features
·
Communication with the control system via IEC 60870-5-104
(Ethernet interface, X1 or X4, can be set by parameter)
·
Communication with the protective devices via IEC 61850
(Ethernet interface, X1 or X4, can be set by parameter)
·
2 IP addresses
·
2 logically separated subnets
─ Communication only visible on the LAN within the subnet
─ Data exchange between subnets only via SICAM A8000 application function
·
1 default router
·
Parameter
2 IP addresses (independent ports)
(in this case both Ethernet interfaces have different MAC addresses)
Office Zone
Control Center Zone
Substation Zone
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Network settings | IP adress | Mode of Ethernet Ports
CP-8000
CP-8021
CP-8022
E SC
Control Center
IP address
Subnet mask 255.255.0.0
Router
IP address
172.16.0.254
PREx / ET84
IP address
X1
Subnet mask
Default router
PREx / ET83
IP address
X4
Subnet mask
Default router
Switch
Unrestricted
Use Cases
=
172.17.0.22
172.16.0.3
255.255.0.0
172.16.0.254
192.168.1.130
255.255.255.0
172.16.0.254
IP address
192.168.1.n
589