Preparing the Engineering
7.7.2.2

Communication with the Target Device

For the parameterization the target device must be connected with the engineering PC and
switched on. In the Master Module of the target device a SD card must be equipped.
The establishing of a communication connection between engineering PC and the target
device takes place via adjustable IP addresses. For the initial parameter setting of
CP-8000/CP-802x, default IP addresses are available. These are specific for the respective
physical connection.
With local engineering, fixed IP addresses are used since they are required only temporarily
for the parameterization of the target device.
Default IP Configuration in CP-8000/CP-802x
Parameter
<Own IP address>
Autoconfiguration
Mode of the Ether-
net ports
Parameter "Mode of
the Ethernet ports"
Own IP address
Subnet mask
Default gateway
Network connection
262
Unrestricted
Value
Meaning/Remark
172.16.0.1
Address of CP-8000/CP-802x web server via
serial interface X2 (fixed)
NO
Configuration via DHCP service deactivated
1 IP address (con-
Common IP address ON Ethernet interfaces X1
nected ports in switch
and X4
mode)
display (selection)
Mode for X1 and X4 can be selected (configura-
tion of separate IP addresses enabled)
172.16.0.3
Address of CP-8000/CP-802x web server via
Ethernet interface X1 and X4
255.255.255.0
0.0.0.0 = not used
0.0.0.0
0.0.0.0 = not used
In practice the default gateway is assigned on
the smallest (193) or greatest (222) usable IP
address in the network.
If the own network is connected via a router, the
address of the router is to be set.
LAN
Utilized transmission media
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual