Preparing the Engineering
7.8.2.9

Exceptions with Engineering via SICAM WEB

The parameter records in the SICAM TOOLBOX II and in the SICAM WEB are basically iden-
tical structured. However, for the engineering via SICAM WEB some simplifications exist,
hence the following functions are not supported or implemented in another manner:
·
HW configuration Master Module
The Master Module is automatically configured as soon as a SD card with the firmware
CPC80 has been installed.
·
System technique I/O Master Module
After the configuration of the I/O Master Module the I/O Modules must be configured in the
OPM II. With the engineering via SICAM WEB the I/O Modules are configured automati-
cally.
·
Process technique I/O Master Module
In contrast to the OPM II no images are applied, for each I/O Module an assignment page
and a parameter page exist.
In the assignment page the usage of the I/Os is defined (according to the assignment in
the SICAM TOOLBOX II).
In the setting page the previously configured I/Os are parameterized. There appear only
the parameters relevant for the defined usage.
·
Process technique protocol element
In contrast to the OPM II no images are applied, the process technique is provided as
spreadsheets (send detailed routing, receive detailed routing).
·
Loading firmware of protocol elements
Protocol elements can not be loaded slot-selectively. If for instance on PRE0 and on PRE1
the system element UMPST0 is configured, both are loaded.
·
Message simulation
The message simulation is not supported (inserting of arbitrary messages into the sys-
tem). However, there is the possibility of displaying current process values of the periphery
(binary information states, integrated totals, measured values) and to set process values
(commands, setpoint commands).
·
Data flow test
The data flow test is not supported (different log points, filters, etc.).
·
Revision interrogation
The current firmware revision of the Master Module is displayed in the header of the user
interface, the revisions of the additional system elements (protocol elements, I/O Master
Module) in the drop-down menu on the configuration page.
·
Application program
A graphical function diagram (FUD) creation is not possible, only an instruction list (IL) with
ASCII format can be loaded into the target device.
·
Test of the application program
Offline simulation of the application program is not possible. A simplified online test (state
display, forcing of a selectable signal) is available.
282
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017