Siemens CP-8000 User Manual page 379

Sicam a8000 series
Hide thumbs Also See for CP-8000:
Table of Contents

Advertisement

Processing type
DO_DC_2POL – double
command output 2-pole
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Parameter
Sync_Input_t_1
1_out_of_n_t_1
Sw_Seq_command_seq_0
Sw_Seq_addtl_com_0
Sw_Seq_command_seq_1
Sw_Seq_addtl_com_1
RS_Mon_Source_0
RS_Mon_Source_1
SID-BSE
SID-ST
SID-SSE
QOC>8
ON_before_OFF
Regulating_command
RS_Image
Retry_suppression_T
Engineering via SICAM WEB
Meaning
Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation
input.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Switching sequence: output additional com-
mand before or after the command
Switching sequence: Select the additional
command
Switching sequence: output additional com-
mand before or after the command
Switching sequence: Select the additional
command
Source of state information for state infor-
mation monitoring
· Peripherals
· Open-/closed loop control function
· Both (logical OR)
Source of state information for state infor-
mation monitoring
· Peripherals
· Open-/closed loop control function
· Both (logical OR)
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
Definition of the order for the wiring of double
commands/double point information:
· NO: OFF is I/O with lower I/O number ON is
I/O with higher I/O number
· YES: ON is I/O with lower I/O number OFF
is I/O with higher I/O number
Use as regulating command (S)
NO/YES
Parameter works only with ACP 1703 platform
Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
Unrestricted
379

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp-8021Cp-8022

Table of Contents