Engineering via SICAM WEB
Processing type
DI_SI – single-point
information input
DI_CV – count pulse
acquisition
374
Unrestricted
Parameter
Flutt_t_stable
Inversion
block
Flutt_dp_qds
input function
SVM_monitoring
Flutt_Number
SW_Filter_t
Flutt_t
State_of_flutter_information
Delay_t
Moduleselection_SVM_
monitoring
Flutt_t_stable
message_blocking_t
interval_time_0
interval_time_1
Inversion
block
Type
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Meaning
Flutter suppression: stability time in seconds.
0 = stability time defined through parameter
Flutt_t (S)
0.1 to 6553.5
Inversion (S)
NO/YES
Blocking (= not used) (S)
NO/YES
Datapoint quality discriptor for fluttery binary
information
BL/IV
Functionality of the binary input. This parame-
terization permits to disable the information
input for revision handling.
Power monitoring. The sensor voltage is
monitored by an own power monitoring input
(S).
NO/YES
Number of transients for flutter suppression
(S)
Software filter-time in s (S)
Flutter time in seconds.
0 = no fluttersuppression (S)
0.1 to 6553.5
Information state in message with BL bit
Delaytime from ON singlepoint information in
seconds
0 to 16000
Switch for power monitoring handling (PM)
Standard PM (PM inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI module.
Flutter suppression: stability time in seconds.
0 = stability time defined through parameter
Flutt_t (S)
0.1 to 6553.5
Message blocking time in seconds. During this
time period, identical messages will be dis-
carded without error information.
0.1 to 6553.5
Interval time. As transmission trigger or latch
trigger of the counts it is also possible to set
an interval. The belonging time is to configure
here.
Interval time. As transmission trigger or latch
trigger of the counts it is also possible to set
an interval. The belonging time is to configure
here.
Inversion (S)
NO/YES
Blocking (= not used) (S)
NO/YES
Conditioned value type (S)
DC8-037-2.02, Edition 10.2017