Engineering via SICAM WEB
9.1.12
Usage of CP-8000/CP-802x as SICAM PAS I/O
The devices CP-8000/CP-802x can be used as non-licensed SICAM PAS substations. The
differentiation between normal operation and operation as SICAM PAS I/O is done via a pa-
rameter.
With operation as SICAM PAS I/O, the IEC 60870-5-104 protocol element is defined as a
SICAM PAS I/O interface upon startup. All stations that are connected with this protocol ele-
ment are switched to SICAM PAS I/O mode. A connection with a normally operated station on
the same protocol element is not possible.
Prerequisite for the operation as SICAM PAS I/O is an equipped IEC 60870-5-104 protocol el-
ement (in the following example PRE0 is used).
Set in the directory
parameter project specific settings
Now appears the directory
PRE0 | project specific
YES.
For the operation as SICAM PAS I/O the following parameters are relevant:
·
SICAM A8000 CP-80xx | Master module | AU common settings
─
Plant
─
Device name
·
SICAM A8000 CP-80xx | Master module | AU common settings | common address of
ASDU (CASDU)
─
CASDU1
─
CASDU2
·
SICAM A8000 CP-80xx | Master module | Network settings | IP address
─
Own IP address X1/X4
·
SICAM A8000 CP-80xx | Master module | PRE0 | Network connection | LAN | IEC 104
parameter
─
Timeout connection setup t0
─
Timeout transmit t1
─
Timeout transmit acknowledge t2
─
Timeout connection check t3
─
Max. no. of APDUs until acknowledgement (k)
─
number of APDUs until acknowledgement (w)
406
Unrestricted
SICAM A8000 CP-80xx | Master module | Communication | PRE0
SICAM A8000 CP-80xx | Master module | Communication |
settings. Here you can set the parameter SICAM PAS IO mode to
(must be set equally for all data points)
(must be set equally for all data points)
to YES.
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
the