Parameter
Ring waves 100 kHz
Conducted common mode
disturbances
Voltage ripple DC
Damped oscillotory waves
1 MHz
Damped oscillotory waves
1 MHz
Damped oscillotory waves
1 MHz
Damped oscillotory waves
1 MHz
Voltage dips, short-time
interruption and voltage
fluctuations on DC input
connections
*)
for interruptions/fluctuations > 50 ms applies criterion B: restart of the device allowed
(CP-8000: > 100 ms)
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Value
2.0 kVp
normal
30...3 V
common
15 Hz...150 kHz
30 V
16⅔/50/60 Hz 60 s
300 V
16⅔/50/60 Hz 1 s
10% U
N
2.5 kVp
common
2.5 kVp
normal
2.5 kVp
common
2.5 kVp
transverse
Dikps: (∆Un)
30% 100ms
30% 500ms
60% 100ms
60% 500ms
Interruptions: (∆Un)
100% 10ms
100% 50ms
100% 100ms
100% 500ms
100% 5s
Test standard
Product standard Class
IEC 61000-4-12
IEC 60870-2-1
IEC 61000-4-16
IEC 61000-4-17
IEC 60870-2-1
IEC 61000-4-18
IEC 60870-2-1
IEC 61000-4-18
IEC 60870-2-1
IEEE C37.90.1
IEEE C37.90.1
IEC 61000-4-29
IEC60870-2-1
IEC 61850-3 Ed.2
Unrestricted
Ambient Conditions
>3
>VR3
4
>4
81