7.7.2.2.3 LAN/WAN Connection via Ethernet Interface

The following steps are necessary:
·
Writing IP address with Sicam_first_startup
·
Connection setup via SICAM WEB
Configure IP Address with Sicam_first_startup
With operation in a network, an unambiguous IP address must be assigned to each connected
CP-8000/CP-802x. The assignment of the IP address is dependent on the subnet mask used
in the network.
The identification for the assignment of the IP address happens solely via the MAC address of
the target device. This is printed on the type plate at the left side of the housing, or it can be
read also on the display under the menu Device information.
Note
The IP address can be assigned with the tool Sicam_first_startup within a network segment (subnet). This
can happen also if the IP address of the engineering PC is located out of this subnet. On the other side,
the assignment of the IP address via a routed network (PC and target device separated via a router) is not
possible.
For the address assignment start the program Sicam_first_startup.exe with double click.
The Sicam_first_startup splash screen is opened, and the Sicam_first_startup symbol appears in
the notification area of the taskbar:
·
Click on the splash screen in order to close it
·
Click then with the right mouse button on the Sicam_first_startup symbol
The context menu of Sicam_first_startup is opened:
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Preparing the Engineering
Unrestricted
265