Parameter
select_execute_t
Fail_behav
block
X_0%
X_100%
Y_0%
Y_100%
receive format
termination_t
SID-BSE
SID-ST
SID-SSE
Engineering via SICAM WEB
Meaning
1000000000000000.000
Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary. 0 = no select command is
expected (direct command transmission)
0 to 6553.5
Behavior at failure
· Keep
· Substitute value
Blocking (=not used) (S)
NO/YES
Nominal range in the physical unit of the
input/output (0%) (S)
-10.0 to 10.0
Nominal range in the physical unit of the
input/output (100%)
-10.0 to 10.0
Technological or normalized value 0% (S)
-1000000000000000.000 to
1000000000000000.000
Technological or normalized value 100% (S)
-1000000000000000.000 to
1000000000000000.000
Source of datapoint
spontaneous
Time between confirmation and termination (s)
0 = no termination
0 to 6553.5
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
Unrestricted