11.5.1.2 Importing Master Data into the SICAM TOOLBOX II

New firmware codes can be loaded into the SICAM TOOLBOX II with the tool "Master Data
Update". Thereto belong
·
Libraries for the tool OPM II
·
Firmwares of SICAM RTUs system elements
You find the details thereto in the SICAM TOOLBOX II Online Help, chapter "OPM II", section
"Master Data Update".
An additional option provides the tool "Live Update". You find the information thereto in the
SICAM TOOLBOX II Online Help, chapter "Service Programs", section "Live Update".
11.5.1.3 Loading Firmware Codes into the Target Device
Firmware codes that are stored in the SICAM TOOLBOX II can be loaded into a target device.
11.5.1.3.1 Loading Firmware Online
For the accomplishment the engineering PC must be connected with the target device, and a
suitable SD card must be inserted in the target device. The configuration options listed in sec-
tion 7.7.1,
SICAM TOOLBOX II
Note
A serial connection via modem is not supported.
With the tool "Load Firmware" ( TOOLBOX II | Service Programs ) you can load firmware
codes into the target device. The following options are available:
·
Load intelligent
The latest firmware revision available in the SICAM TOOLBOX II is loaded, if it is more
current than that one on the corresponding system element
·
Load unconditional
The latest firmware revision available in the SICAM TOOLBOX II is loaded
You find the instructions thereto in the SICAM TOOLBOX II Online Help, chapter "Service
Programs", section "Load Firmware".