Service
With the initial reading in a session, the 30 most current entries are displayed.
·
Click on the button
Thereupon, the next older indications are loaded and displayed. As long as not all indications
have been loaded, the button remains activated.
The error table captures up to 10000 entries and is stored non-volatile. If the error table is full,
the respective oldest entry will be overwritten with the most current one (ring buffer).
If you select a row of the table, an area with more detailed information is opened on the right
side.
·
Click on the sidebar right beside the table, if you want to hide the detailed description of
the selected entry
Note
When reopening the diagnosis logbook page within the same session, the displayed indications will not be
refreshed.
This is how to update diagnosis logbook indications:
·
Click on the general button
the device
The existing table will be deleted and only those entries which have been created by the de-
vice since the last reading procedure will be read out from the device and will be listed in a ta-
ble.
510
Unrestricted
, if you want to see entries with an earlier timestamp
for reading again all diagnosis logbook indications from
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017