Processing type
DO_SC_2POL – single
command output 2-pole
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
Parameter
Sw_Seq_addtl_com
SID-BSE
SID-ST
SID-SSE
QOC>8
RS_Image
Retry_suppression_T
Output_t
select_execute_t
Sync_t
RS_Mon_t
Command_prolong_t
RS_outp_same_state_1
Sync_Input_t
1_out_of_n_t
Engineering via SICAM WEB
Meaning
Switching sequence: Select the additional
command
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254; if
automatic, the SID will be learned
Source identification supplementary system
element
If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
Parameter works only with ACP 1703 platform
Command retry suppression time in seconds.
Within this time a command with same ad-
dress is discarded without error information (s)
0.1 to 6553.5
Command output time in seconds (S).
Attention: The time comes into effect only, if in
the message is not defined any time.
0.01 to 327.67
Max. time between select and execute (in
seconds). After this time a recent select com-
mand is necessary.
0 = no select command is expected (direct
command transmission)
0.1 to 102.3
Within this time (in sec) the interlock enabling
must occur on the command.
0 = no syncronisation over interlocking
0.1 to 6553.5
Return state information monitoring time in
seconds (S).
0 = no return state information monitoring
0.01 to 655.35
Command prolongation time in seconds (S)
0.01 to 327.67
Selection of command output and command
confirmation, if return state is already end
position before output.
Attention: only active if RS_mon_t is ≠ 0.
Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation
input.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Unrestricted
385