Click on the general button
In case of error, please consider the conventions described in section
struction List
This is how to activate an IL in the target device:
The changed data must be saved, otherwise the IL will be rejected when leaving the session.
·
Click on the general button
The application programm will be saved on the SD card. After the saving, a
get device is required.
During startup the newly loaded program code is compiled,checked and written in the program
memory. An already present program code is thereby overwritten.
·
If no error is present, the program is processed after startup.
·
If an error is present, the program is shut down and an error indication is recorded in the
diagnosis and in the history.
Note
For the transmission via Ethernet, it is recommended to deactivate the settings for HTTP 1.1 of your PC
(Control Panel, Internet Options, tab "Advanced"). Otherwise the possibility exists that CP-8000/CP-802x
can not interprete the transmitted ASCII file.

9.2.2.1.2 Load Application Programm Offline

For instance, in course of an initialization of the target device (refer to
Firmware) you can copy an instruction list saved as ASCII file from your PC directly on the SD
card.
·
Insert the SD card in a read/write device installed on the engineering PC
·
Copy the program file in the root directory of the SD card
·
Change the file name to case plc_src.plc
·
After that, insert the SD card into the target device
The target device performs a startup and checks therteby the program code:
·
If no error is present, the program code is compiled and written into the program memory.
If present, the existing program code is thereby overwritten. After the startup, the new pro-
gram code will be processed.
·
If an error is present, an error indication with details is recorded in the history. If present,
the existing program code is maintained and executed again after startup.
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
, if you want to read the status log
(IL).
, if you want to save the IL
Engineering via SICAM WEB
9.2.1, Creating an In-
restart
Initialization of the
Unrestricted
of the tar-
437