4.3.4

Cable protection

Cable protection for individual converters
If you individually protect an Inverter, then you must protect the Inverter feeder cable using a
fuse.
Table 4- 6
Rated power
0.37 kW
0.75 kW
1.1 kW
1.5 kW
2.2 kW
3 kW
4 kW
For additional information, please refer to Catalog D31at the following link:
SINAMICS and motors for Single-Axis Drives D31 catalog
(https://intranet.automation.siemens.com/mcms/infocenter/content/en/Pages/order_form.asp
x?nodeKey=key_566000&infotype=catalogs&linkit=null)
Installation using power-through daisy chain
The SINAMICS G110M system has been designed to allow a converter to utilize power-
through to provide the mains power for a number of converters in a daisy chain.
The maximum current limits for the daisy chain are given below:
● For the HanQ variants the maximum current of the daisy chained converters must not
exceed 16 A.
● For the Glanded variants the maximum current on the daisy chained converters must not
exceed 12 A.
● For both HanQ and Glanded variants the input for the daisy chained converters can be
protected by a 20 A fuse.
It is the users responsibility to ensure that the current limits are not exceeded.
The methodology for daisy chaining a number of Inverter is shown in the following diagram.
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Individual fuse protection
Power Module
6SL3517-1BE11-3AM0
6SL3517-1BE12-3AM0
6SL3517-1BE13-3AM0
6SL3517-1BE14-3AM0
6SL3517-1BE16-3AM0
6SL3517-1BE17-3AM0
6SL3517-1BE21-3AM0
4.3 Electrical Installation
Frame size
Fuse
FSA
10 A
FSA
10 A
FSA
10 A
FSA
10 A
FSB
20 A
FSB
20 A
FSB
20 A
Installation
3NA3803
3NA3803
3NA3803
3NA3803
3NA3807
3NA3807
3NA3807
73