When required, you can use the analog inputs as additional digital inputs.
NOTICE
Defective analog input due to overcurrent
If the analog input switch is set to "Current input" (I), a 10 V or 24 V voltage source results in an
overcurrent at the analog input. An overcurrent condition destroys the analog input.
• If you use an analog input as a digital input, then you must set the analog input switch to
8.4.3

Failsafe digital input

Function description
The converter combines digital inputs DI4 and DI5 to create a failsafe digital input.
See also
Connections and cables (Page 46)
8.4.4

Digital outputs

Function description
Interconnect the digital output with a binector output of your choice.
Binector outputs are designated in the parameter list with "BO".
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
"Voltage" (U).
Safe Torque Off (STO) safety function (Page 178)