SIO output function

The ON/OFF status (Y signal) of outputs is controlled with Remote output (RY) of the CC-Link IE Field Network.
To operate the SIO mode for outputs, turn on Channel n (CQ/Q) I/O switching command (RY10 to RY1F) in the initial
processing.
To apply the I/O switching setting changed in processing other than the initial processing and parameter setting on an
engineering tool, turn on Operation condition setting request flag (RWw0.b9).
Setting procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Module Parameter]  [Basic Settings]
 [Network Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module  [CC IE Field Configuration]  [Online]  [Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Parameter Write".
4.
For each channel, set "Write Value" of "Pin configuration setting" to "OUTPUT".
7 FUNCTIONS
76