Drilling template for wall-mounting
Before you can wall-mount LOGO!, you need to drill holes using the template shown below.
All dimensions in mm
Bore hole for Ø M4 screw, tightening torque 0.8 to 1.2 Nm
LOGO! Base Module
LOGO! expansion modules, DM *..., AM...
LOGO! expansion modules, DM 16...
2.2.3

Mounting the LOGO! TD

To prepare the mounting surface for the optional LOGO! TD and mount it, follow these steps:
1. Cut a 119.5 mm x 78.5 mm (tolerance: +0.5 mm) hole in the mounting surface.
2. Place the included gasket on the frontplate of the LOGO! TD.
3. Fit the LOGO! TD into the cutout you made in the mounting surface.
4. Attach the mounting brackets (included) to the LOGO! TD.
5. Tighten the mounting screws on the mounting brackets to 0.2 Nm torque to secure the
LOGO! TD.
LOGO!
Manual, 10/2017, A5E01248535-AA
LOGO! installation and wiring
2.2 Installing/removing LOGO!
35