Siemens LOGO! Manual page 21

Hide thumbs Also See for LOGO!:
Table of Contents

Advertisement

Expansion modules
The following expansion modules can be connected to LOGO!:
Symbol
Different phases are not allowed within the inputs.
1)
0 ... 10 V, 0/4 ... 20 mA can be connected optionally.
2)
Digital inputs can be operated either with P or with N action.
3)
Two groups consisting of 4 inputs each. Each input within a group must be connected to the same
4)
phase. It is possible to interconnect groups with a different phase.
0 ... 10 V, 0/4 ... 20 mA can be connected optionally. The 0/4 ... 20 mA current output is only pos-
5)
sible with the LOGO! 0BA6 Base Module.
Sensors supported by the LOGO! AM2 RTD module are the PT100 and PT1000 sensors with a
6)
default temperature coefficient α of 0.003850.
LOGO!
Manual, 10/2017, A5E01248535-AA
Name
Power supply
LOGO! DM8 12/24R
12/24 V DC
LOGO! DM8 24
24 V DC
LOGO! DM8 24R
24 V AC/DC
3)
LOGO! DM8 230R
115...240 V AC/DC
LOGO! DM16 24
24 V DC
LOGO! DM16 24R
24 V DC
LOGO! DM16 230R
115...240 V AC/DC
LOGO! AM2
12/24 V DC
LOGO! AM2 PT100
12/24 V DC
LOGO! AM2 RTD
12/24 V DC
LOGO! AM2 AQ
24 V DC
Getting started with LOGO!
Inputs
Outputs
4 digital
4 relays (5A)
4 digital
4 solid state 24V /
0.3A
4 digital
4 relays (5A)
4 digital
4 relays (5A)
1)
8 digital
8 solid state
24V / 0.3A
8 digital
8 relays (5A)
8 digital
8 relays (5A)
4)
2 analog
None
0 ... 10V or
0/4 ... 20mA
2)
2 PT100
None
6)
-50 degrees C to
+200 degrees C
2 PT100 or 2 PT1000
None
or 1 PT100 plus 1
PT1000
6)
-50 degrees C to
+200 degrees C
None
2 analog
0 ... 10 V DC or
0/4...20mA
5)
21