Technical data
A.6 Technical data: LOGO! 24RC...
Input current at
Delay time at
Line length (unshielded)
Digital outputs
Number
Output type
Electrical isolation
In groups of
Control of a digital input
Output voltage
Output current
Short circuit-proof and overload-
proof
Short circuit current limitation
Derating
Short circuit-proof cos 1
Short circuit-proof cos 0.5 to 0.7
Parallel output circuit for power
increase
Protection of output relay (if
desired)
Switching rate
Mechanical
Electrical
Ohmic load/lamp load
Inductive load
When LOGO! 24/24o, LOGO! 24C/24Co, LOGO! DM8 24 or LOGO! DM16 24 are switched on,
1)
signal 1 is sent to the digital outputs for about 50 microseconds. Take this into account, especially
when using devices that react to short pulses.
254
Signal 0
Signal 1
0 to 1
1 to 0
LOGO! DM8 24
< 0.85 mA
> 2 mA
typ. 1.5 ms
typ. 1.5 ms
max. 100 m
4
Transistor,
current-sourcing
1)
No
- -
Yes
≤ Supply voltage
max. 0.3 A
Yes
Approx. 1 A
none; across the entire tem-
perature range
- -
- -
Not permitted
- -
- -
10 Hz
10 Hz
0.5 Hz
LOGO! DM16 24
< 0.85 mA
> 2 mA
typ. 1.5 ms
typ. 1.5 ms
max. 100 m
8
Transistor,
current-sourcing
(1)
No
- -
Yes
≤ Supply voltage
max. 0.3 A
Yes
Approx. 1 A
none; across the entire tem-
perature range
- -
- -
Not permitted
- -
- -
10 Hz
10 Hz
0.5 Hz
Manual, 10/2017, A5E01248535-AA