Mechanical
Electrical
Ohmic load/lamp load
Inductive load
When LOGO! 24/24o, LOGO! 24C/24Co, LOGO! DM8 24 or LOGO! DM16 24 are switched on,
1)
signal 1 is sent to the digital outputs for about 50 microseconds. Take this into account, especially
when using devices that react to short pulses.
The maximum switching rate is only dependent on the switching program's cycle time.
2)
A.5

Technical data: LOGO! DM8 24 and LOGO! DM16 24

Power supply
Input voltage
Permissible range
Reverse polarity protection
Permissible mains frequency
Power consumption from 24 V
DC
Power loss at 24 V
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
Max. continuous permissible
voltage
Input voltage
LOGO!
Manual, 10/2017, A5E01248535-AA
2)
Normal input
High speed input
Signal 0
Signal 1
A.5 Technical data: LOGO! DM8 24 and LOGO! DM16 24
LOGO! 24
LOGO! 24o
Not permitted
- -
- -
10 Hz
10 Hz
0.5 Hz
LOGO! DM8 24
24 V DC
20.4 ... 28.8 V DC
Yes
- -
30 ... 45 mA
0.3 A per output
0.8 ... 1.1 W
4
No
0
max. 4 Hz
- -
28.8 V DC
L+
< 5 V DC
> 12 V DC
Technical data
LOGO! 24C
LOGO! 24Co
Not permitted
- -
- -
10 Hz
10 Hz
0.5 Hz
LOGO! DM16 24
24 V DC
20.4 ... 28.8 V DC
Yes
- -
30 ... 45 mA
0.3 A per output
0.8 ... 1.7 W
8
No
0
max. 4 Hz
- -
28.8 V DC
L+
< 5 V DC
> 12 V DC
253