Power consumption
Voltage failure buffering
Power loss at
Backup of the real-time clock at 25 °C
Accuracy of the real-time clock
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
Max. continuous permissible voltage
Input voltage L1
Input current at
LOGO!
Manual, 10/2017, A5E01248535-AA
115 V AC
240 V AC
115 V DC
240 V DC
115 V AC/DC
240 V AC/DC
115 V AC
240 V AC
115 V DC
240 V DC
Normal input
High speed input
Signal 0
Signal 1
Signal 0
Signal 1
Signal 0
Signal 1
Signal 0
Signal 1
A.2 Technical data: LOGO! 230...
LOGO! 230RC
LOGO! 230RCo
15 ... 40 mA
15 ... 25 mA
10 ... 25 mA
6 ... 15 mA
typ. 10 ms
typ. 20 ms
1.7 ... 4.6 W
3.6 ... 6.0 W
1.1... 2.9 W
1.4 ... 3.6 W
typ. 80 hours without battery card
typ. 2 years with battery card
typ. ± 2 s / day
8
No
0
max. 4 Hz
- -
265 V AC
253 V DC
< 40 V AC
> 79 V AC
< 30 V DC
> 79 V DC
< 0.03 mA AC
> 0.08 mA AC
< 0.03 mA DC
> 0.12 mA DC