Pulse Relay - Siemens LOGO! Manual

Hide thumbs Also See for LOGO!:
Table of Contents

Advertisement

LOGO! functions
4.4 Special functions list - SF
4.4.22

Pulse relay

Short description
A short pulse at the input sets and resets the output.
Symbol in LOGO!
Timing diagram
Functional description
Output Q changes its status; that is, the output is set or reset with each 0 to 1 transition at
input Trg and if the inputs S and R = 0.
The signal at input Trg does not influence the special function when S or R = 1.
You set the pulse relay with a signal at input S. The output is set hi.
You reset the pulse relay with a signal at input R. The output is set lo.
176
Wiring
Description
Input Trg
You set and reset output Q with a signal at input Trg
(Trigger).
Input S
You set output Q with a signal at input S.
Input R
You reset output Q with a signal at input R.
Parameter
Selection:
RS (R input priority) or
SR (S input priority)
Retentivity:
/ = No retentivity
R = The status is retentive.
Output Q
Q is set with a signal at Trg, and reset with the next
signal at Trg, if S and R = 0.
Manual, 10/2017, A5E01248535-AA