LOGO! installation and wiring

2.3 Wiring LOGO!

You can then use the included cable to connect the LOGO! TD to the LOGO! Base Module
up to a distance of 2.5 meters. You can extend this distance to up to ten meters by using a
standard Sub-D cable together with the LOGO! TD cable.
2.2.4

Labeling LOGO!

The gray rectangular areas on the LOGO! modules are intended for labeling.
In the case of expansion modules, you can use the gray areas for labeling the inputs and
outputs, for example. In this connection, you can enter a delta factor of +8 for the inputs or
+4 for the outputs if the LOGO! Base Module already has 8 inputs or 4 outputs.
2.3
Wiring LOGO!
Wire LOGO! using a screwdriver with a 3-mm blade.
You do not need wire ferrules for the terminals. You can use conductors with cross-sections
of up to the following thicknesses:
● 1 x 2.5 mm
● 2 x 1.5 mm
Tightening torque: 0.4...0.5 Nm or 3...4 in-lbs.
Note
Always cover the terminals after you have completed the installation. To protect LOGO!
adequately from impermissible contact to live parts, comply with local standards.
36
2
for each second terminal chamber
2
Mounting brackets
Mounting screws
Gasket
Cabinet door or control panel
(Thickness: 1.5 to 4 mm)
Manual, 10/2017, A5E01248535-AA