4.4.13

Up/down counter

Short description
An input pulse increments or decrements an internal value, depending on the parameter
setting. The output is set or reset when a configured threshold is reached. The direction of
count can be changed with a signal at input Dir.
Symbol in LOGO!
LOGO!
Manual, 10/2017, A5E01248535-AA
Wiring
Description
Input R
A signal at input R resets the internal count value to
zero.
Input Cnt
The function counts the 0 to 1 transitions at input Cnt.
1 to 0 transitions are not counted.
Use
Input Dir
You set the direction of count at input Dir:
Dir = 0: Up count
Dir = 1: Down count
Parameter
On: On threshold
Range of values:
0...999999
Off: Off threshold
Range of values:
0...999999
StartVal: Initial value from which to begin counting
either down or up.
Retentivity for internal counter value Cnt:
/ = No retentivity
R = The status is retentive.
Output Q
Q is set or reset, depending on the current value at
Cnt and the set thresholds.
4.4 Special functions list - SF
inputs I3, I4, I5, and I6 for fast counting (only
LOGO! 12/24RC/RCo, LOGO! 24/24o and LOGO!
24C/24Co): max. 5 kHz.
any other input or circuit component for counting
low frequency signals (typ. 4 Hz).
LOGO! functions
151