A.6
Technical data: LOGO! 24RC...
Power supply
Input voltage
Permissible range
Reverse polarity protection
Permissible mains frequency
Power consumption
•
•
Voltage failure buffering
Power loss
•
•
Backup of the real-time clock at 25 °C
Accuracy of the real-time clock
Digital inputs
Number
Electrical isolation
Number of high speed inputs
Input frequency
•
•
Max. continuous permissible voltage
Input voltage
•
•
Input current at
•
•
Delay time at
•
•
Line length (unshielded)
Analog inputs
Number
LOGO!
Manual, 10/2017, A5E01248535-AA
24 V AC
24 V DC
24 V AC
24 V DC
Normal input
High speed input
Signal 0
Signal 1
Signal 0
Signal 1
0 to 1
1 to 0
A.6 Technical data: LOGO! 24RC...
LOGO! 24RC
LOGO! 24RCo
24 V AC/DC
20.4 ... 26.4 V AC
20.4 ... 28.8 V DC
- -
47 ... 63 Hz
45 ... 130 mA
•
40 ... 100 mA
•
typ. 5 ms
1.1... 3.1 W
•
1.0 ... 2.4 W
•
typ. 80 hours without battery card
typ. 2 years with battery card
typ. ± 2 s / day
8,
optional P action or N action
No
0
max. 4 Hz
•
- -
•
26.4 V AC
28.8 V DC
L
< 5 V AC/DC
•
> 12 V AC/DC
•
< 1.0 mA
•
> 2.5 mA
•
typ. 1.5 ms
•
typ. 15 ms
•
max. 100 m
- -
Technical data