Functional description
The function fetches the analog values from the inputs Ax and Ay.
Ax and Ay are each multiplied by the value of the A (gain) parameter, and the value at
parameter B (offset) is then added to the relevant product, i.e.
(Ax • gain) + offset = actual value Ax or
(Ay • gain) + offset = actual value Ay.
The function forms the difference ("Δ") between the actual values Ax - Ay.
Output Q is set or reset, depending on difference of the actual values Ax - Ay and the set
thresholds. See the calculation rule below.
Calculation rule
● If the On threshold ≥ Off threshold, then:
Q = 1, if:
(actual value Ax - actual value Ay) > On
Q = 0, if:
(actual value Ax - actual value Ay) ≤ Off.
● If the On threshold < Off threshold, then Q = 1, if:
On ≤ (actual value Ax - actual value Ay) < Off.
Setting the Par parameter
The gain and offset parameters are used to adapt the sensors to the relevant application.
View in programming mode: