Technical Data

11.4 Recorder Functions

11.4
Recorder Functions

Fast-Scan Recorder

11.4.1
Setting Values
Fast-Scan Recorder
Memory capacity
Maximum record time
Pre-trigger time
Post-trigger time
Manual record time
Sampling frequency
Retrigger blocking time
Number of Recorder Instances
Fast-scan recorder
Signals to be Recorded
Refer to
Number of Routable Measured Values (MV) and Binary Tracks (SPS), Page 439
Trigger
Frequency trigger
Power trigger
Voltage trigger
Current trigger

Slow-Scan Recorder

11.4.2
Setting Values
Slow-Scan Recorder
Memory capacity
Maximum record time
Pre-trigger time
Post-trigger time
Manual record time
Averaging time
Retrigger blocking time
Number of Recorder Instances
Slow-scan recorder
Signals to be Recorded
Refer to
Number of Routable Measured Values (MV) and Binary Tracks (SPS), Page 439
Trigger
Frequency trigger
438
Setting Range
0.200 GB to 15.000 GB
1.0 s to 90.0 s
0 s to 3.0 s
1.0 s to 90.0 s
1.0 s to 90.0 s
1 kHz to 16 kHz
0.0 s to 3600 s
1 (fix)
Setting Range
0.200 GB to 14.800 GB
1 min to 90 min
0 s to 90 s
1 min to 90 min
1 min to 90 min
1 to 3000 periods
0 min to 240 min
0 to 2
Increment
Increments of 1
Increments of 0.1
Increments of 0.1
Increments of 0.1
Increments of 0.1
Increments of 1, 2, 4, 8, 16
Increments of 0.1
Increment
Increments of 1
Increments of 1
Increments of 1
Increments of 1
Increments of 1
Increments of 1
Increments of 1
SIPROTEC 5, Fault Recorder, Manual