Siemens SIPROTEC 5 Manual page 233

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Configuration of Stored Indications with DIGSI 5
In the Information routing of each device set up in DIGSI 5, you can route binary signals to LEDs and
output contacts. For this open in the project tree.
Project → Device → Information Routing
Click with the right mouse button on the routing field of your binary indication in the desired LED or
binary output column in the routing range of the targets.
You are offered the following options:
Table 7-4
Routing Options
LED
(unrouted)
X
X
(routed)
H
Active with
voltage
L
Active without
voltage
V
Unlatched
X
G
Latched
X
V
Toggle
P
(Trigger pulse)
On
On
Off
Off
10
Binary input
11
Binary output
12
Function key
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Overview of Routing Options
Description
BI
10
BO
11
FK
12
X
X
X
The signal is not routed.
X
The signal is routed.
X
There is a voltage applied at the routed binary input
X
X
There is no voltage applied at the routed binary input
X
The signal is routed as unsaved. Activation and reset of the output
(LED, BO) occurs automatically via the binary-signal value.
X
The binary signal is latched when the output (LED, binary output) is
activated. To reset, a targeted confirmation must occur.
X
With this routing option, the trigger rises with the first operational
handling (LED on). When the function key is activated again, the
trigger clears (LED off).
This setting applies for the controllable
inputs
X
With this routing option, the trigger rises and clears. The LED display
illuminates approx. 200 ms.
This setting applies for the binary inputs
>Manual start .
This routing option is practical for a routing of the function key to
>Manual start .
X
This setting applies only for the controllable
X
This setting applies only for the controllable
>External start and >Manual start .
Fault Recorder
7.2 Function-Group Type Recorder
Start record and binary
>External start and
Start record .
Start record .
233

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siemens 7ke85

Table of Contents